Technical parameter table of AC and DC energy storage container below DC1000V+AC400V AC PCS
MODEL | 10FT-401KWH | 20FT-1204KWH | 40FT-3211KWH | 10FT-522KWH | 20FT-1567KWH | 40FT-3134KWH |
200KW | 500KW | 1000KW | 250KW | 500KW | 1500KW | |
DC System | ||||||
Battery cell type | Lithium iron phosphate | |||||
Battery cell specification | 3.2V280AH | 3.2V314AH | ||||
System battery configuration | 224S2P | 224S6P | 224S16P | 260S2P | 260S6P | 260S12P |
Battery capacity | 401kWh | 1204kWh | 3211kWh | 522kWh | 1567kWh | 3134kWh |
Maximum power | 200KW | 500KW | 1000KW | 250KW | 500KW | 1500KW |
Maximum current | 280A | 840A | 2660A | 314A | 942A | 1884A |
Battery rated voltage | 716.8V | 832V | ||||
Battery voltage range | 627V-806V | 728V-936V | ||||
Battery Cluster | ||||||
Battery configuration | 224S1P | 260S1P | ||||
Battery capacity | 200.704kWh | 261.248kWh | ||||
Maximum power | 100KW | 130KW | ||||
Maximum current | 140A | 157A | ||||
Battery rated voltage | 716.8V | 832V | ||||
Battery voltage range | 627V-806V | 728V-936V | ||||
Battery Module | ||||||
Battery configuration | 16S1P | 20S1P | ||||
Battery capacity | 14.336kWh | 20.096kWh | ||||
Maximum power | 7KW | 10KW | ||||
Maximum current | 140A | 157A | ||||
Battery rated voltage | 51.2V | 64V | ||||
Battery voltage range | 44.8V-57.6V | 56V-72V | ||||
AC (on-grid and off-grid) | ||||||
Maximum power (kVA) | 220KVA | 550KVA | 1100KVA | 275KVA | 550KVA | 1500KVA |
Active power (kW) | 200KW | 500KW | 1000KW | 250KW | 500KW | 1650KW |
Rated current (A) | 288A | 722A | 1444A | 361A | 722A | 2166A |
Rated voltage (V) | AC400V | |||||
Voltage range | AC340V-AC460V | |||||
Rated frequency | 50Hz/60Hz | |||||
THDI | 3% | |||||
Power factor | >0.99 (rated power) | |||||
AC standard | Three-phase four-wire + ground wire (3W+N+PE) | |||||
Overload capacity | 110% | |||||
PV Side (optional) | ||||||
Maximum power | 120KW/240KW | 600KW/660KW/720KW | 1200KW/1320KW/1440KW | 300KW/360KW | 600KW/660KW/720KW | 1800KW/1980KW/2160KW |
PV voltage | DC250V-DC850V | |||||
Load Uninterrupted (STS) | (Some are optional, some are standard) | |||||
STS power | 200KW | 500KW | 1000KW | 250KW | 500KW | 1500KW |
STS voltage | 400V 50HZ/60HZ | |||||
Overload power | 110% | |||||
Switching time | <20mS | |||||
System Operation Strategy | ||||||
Functionality | Anti-backflow, black start | |||||
Operation mode selection | Power peak shaving and valley filling, peak and valley arbitrage of electricity prices, photovoltaic priority to save | |||||
electricity bills,wind power generation priority to save electricity bills, off-grid power supply in remote areas | ||||||
Operation scenario | Photovoltaic diesel storage project, wind power diesel storage project, wind photovoltaic diesel storage project, | |||||
charging pile + energy storage project, online electricity sales project | ||||||
General Parameters | ||||||
Cabinet dimensions(w*d*h)mm | 2991*2436*2591 | 6058*2436*2591 | 12192*2436*2591 | 2991*2436*2591 | 6058*2436*2591 | 12192*2436*2591 |
Weight | ≈8.9t | ≈18.6t | ≈43.4t | ≈9.7t | ≈20.5t | ≈44.2t |
Maximum cycle efficiency | ≥95% | |||||
IP rating | IP55 | |||||
Auxiliary power supply | Self-powered/externally powered | |||||
Corrosion resistance level | C3-C5 | |||||
Working humidity range | 0 % – 100 % (no condensation) | |||||
Working temperature range | -30 ℃ – 50 ℃ (> 45 ℃ derating) | |||||
Maximum working altitude | 2000 m | |||||
Battery cabinet cooling method | Intelligent air cooling | |||||
Fire safety configuration | Smoke detectors, temperature detectors, aerosol fire extinguishers, | |||||
pressure relief valves ,PACK level fire protection, cluster level fire protection, | ||||||
water fire protection, automatic pressure relief | ||||||
Communication | Ethernet, 485, CAN | |||||
Communication protocol | Modbus TCP/IP |